Fans Selection

loading

INTRODUCTION

Fans can be selected by three different methods.

  • In the planning stage a quick overview is achieved using the quick selection tables combined with the overview charts in the chapters “Axial Flow Fans” and “Centrifugal Fans”.
  • For more detailed selection, the nomogram can be the method of choice.
  • An exact selection with a complete technical documentation is offered by using the computer based on the WITT INDIA fan selection programme – or our quotation.
  • In the following we would like to give some practical guidelines. For a more complete introduction to fan technology and sound engineering please refer to section �Fan Technology� in our catalogue.

FAN CURVES

All fan curves relate to single stage fans. The standard fan curves are measured on a standard test chamber acc. to DIN 24 163 with free inlet and outlet. All data refer to standard air density = 1.2 kg/m3.

Disturbed inlet and/or outlet lead to pressure losses and volume flow rate reductions, which have to be taken into account when specifying the fan data.

Installation Resistance Curve

Every installation has a characteristic resistance curve, which often resembles a parabola with a more or less pronounced displacement.

Operating Point

The intersection between the resistance curve and the fan curve is the operating point (also called working point). When selecting the fan, one tries to put the operating point close to the point at highest efficiency of the fan curve in order to minimise power consumption and noise generation.

For axial flow fans and some other type of fans it is furthermore important to ensure that the fan never will operate in it's stall area.

Shaft Power

The fan shaft power is calculated as follows:

loading

Where:

loading is the volume flow rate in m3/h

loading is the total pressure increase in Pa

loading is the fan efficiencyin the operating point.

Motor Reserve

The resistance curve is often not well known. It may, due to air density variations, be subject to large variations. If no special conditions prevail a rough guideline is to have a motor reserve of 10 ? 15 % for axial fans and 10 to 25 % for radial fans.

Tip Speeds

Most of WITT INDIA impellers have been optimised using finite element simulations. Depending on the impeller material used the fan tip speed is the main limiting factor for the maximum permissible fan speed. The appendix to the computer fan selection programme describes the WITT INDIA maximum tip speed limits for normal applications. If higher values are needed, please inquire. With technical changes and different material selection higher values can be achieved.

Total pressure increase over the fan Installation type acc. to ISO 5801

Total Pressure iIcrease:

loading

Total Pressure increase:

loading

When the inlet area is equal to the outlet area, then

loading

Total Pressure Increase:

loading

When the inlet area is equal to the outlet area, the total pressure increase "pt" is equal to the static pressure increase "ps".

OUR FAN SELECTION

The use of the various fan selection methods by the client should only be employed for preselection. For the final selection the necessary data acc. to DIN 24 166 should be given to one of our sales engineers to select the most appropriate fan for the desired application.

Data Sheets

To avoid want of clearness we have developed general axial and centrifugal data sheets, with which the complete delivery scope can be specified. We ask the customers to carefully check whether the fans offered are satisfactory in all aspect and if in doubt ask for clarification.